Commercial cooling is driven by what happens inside the building, not by its volume. An open-plan office runs 300–400 sq ft per ton, a restaurant dining room 150–250, a conditioned warehouse up to 1,500. Use these figures to budget and to sanity-check a quote — then have a Manual N or ASHRAE calculation done for the real design.

Cooling load by building type

Building typeSq ft per tonBTU/h per sq ftDriver
Office, open plan3004003040Moderate occupancy, high plug load
Office, private3504502734Lower density
Retail store2503503448Lighting and door traffic
Restaurant, dining1502504880High occupancy, makeup air
Restaurant, kitchen10015080120Cooking equipment dominates
Classroom2003004060Dense occupancy in bursts
Medical / dental2503503448Equipment plus ventilation
Warehouse, conditioned8001500815Envelope-driven, low internal gain
Gym / studio10020060120Very high metabolic load

Ranges assume a reasonably modern envelope in a temperate climate. Hot climates, single glazing and west-facing glass all push toward the low end of the sq-ft-per-ton column.

Server rooms are sized differently

IT heat load   BTU/h = IT power (kW) × 3,412
               tons  = IT power (kW) × 0.284

10 kW of racks → 34,120 BTU/h → 2.8 tons, before UPS losses and envelope

Nearly all electrical power drawn by IT equipment leaves as heat, so the load follows the meter rather than the floor plan. Add UPS and transformer losses, lighting and any envelope gain, then size for redundancy — that is usually what decides the equipment.

What a full commercial calculation adds

  • Outdoor air. ASHRAE 62.1 sets ventilation by occupancy and floor area; conditioning that air is often the largest single load in a dense space.
  • Occupancy schedules. Zones peak at different hours, so the plant is sized on a block load that is smaller than the sum of zone peaks.
  • Internal gains. Lighting, plug loads, kitchen equipment and process heat, each with its own diversity factor.
  • Latent load. Occupancy and outdoor air drive moisture that a sensible-only estimate ignores entirely.
  • Zoning and control. How the load is split decides equipment selection as much as its total size.

Our room-by-room load calculator covers none of that — it is a residential-scale estimate. For a single small commercial space it will get you in the right range; for anything you quote from, it will not.

FAQ

How do you calculate a commercial HVAC load?
A proper commercial calculation follows ACCA Manual N or ASHRAE procedures: envelope gains hour by hour, occupancy density and schedule, lighting and plug loads, process equipment, and outdoor air per ASHRAE 62.1. The result is a peak load per zone plus a block load for the plant — the two differ, because zones do not peak at the same hour. Rules of thumb per square foot are for budgeting and sanity checks only.
How many square feet per ton for a commercial building?
It depends entirely on occupancy. A conditioned warehouse can run 800–1,500 sq ft per ton, an open-plan office 300–400, a restaurant dining room 150–250, and a commercial kitchen 100–150. Quoting a single number across building types is the most common way these estimates go wrong.
How do I size cooling for a server room?
By the IT load, not the floor area. Electrical power drawn by the equipment converts almost entirely to heat: 1 kW of IT load is 3,412 BTU/h, so a 10 kW rack needs about 34,000 BTU/h — nearly 3 tons — before adding UPS losses, lighting and envelope gains. Redundancy requirements usually drive the final selection more than the load itself.
What about clean rooms?
Clean rooms are sized by air change rate and filtration, not by cooling load alone. ISO class sets the required air changes — anywhere from about 20 per hour at ISO 8 to several hundred at ISO 5 — and the fan energy needed to move that air often becomes a large part of the cooling load itself. That is specialist design work.
Can I use the room calculator on this site for a commercial job?
For a first sanity check on a single small space, yes. For anything you will quote or build from, no: it has no model for outdoor air, occupancy schedules or process equipment, and commercial permits generally require a documented Manual N or ASHRAE-based calculation.