What duct size for 1,000 CFM?

1,000 CFM needs a 14-inch round duct at the standard 0.10 in/100 ft friction rate — the exact diameter works out to 13.9 in, at 935 fpm. For long or quiet runs, step up to 16 inches.

Size by design friction rate

Friction (in/100 ft)Exact ⌀Standard sizeVelocity (fpm)
0.0516 in16 in716
0.0814.5 in16 in716
0.1013.9 in14 in935
0.1512.8 in14 in935

Rectangular options

Rectangular ducts equivalent to the 13.9-inch round requirement. Only buildable shapes are listed — nothing narrower than 4 inches or beyond a 4:1 aspect ratio.

Duct sizeEquivalent ⌀
22 × 8 in14.1 in
17 × 10 in14.1 in
14 × 12 in14.2 in

FAQ

What size duct do I need for 1,000 CFM?
A 14-inch round duct at the standard 0.10 in. w.c. per 100 ft friction rate — the exact calculated diameter is 13.9 in, and the next standard size up is 14 in. Air moves through it at 935 fpm.
What if the run is long or noise matters?
Design at a lower friction rate. At 0.05 in/100 ft the same 1,000 CFM needs a 16-inch duct — larger, but quieter and with less pressure loss over a long run.
How many tons of cooling is 1,000 CFM?
At the standard 400 CFM per ton, 1,000 CFM corresponds to about 2.5 tons. Humid climates design closer to 350 CFM per ton, dry climates up to 450.