What duct size for 300 CFM?

300 CFM needs a 9-inch round duct at the standard 0.10 in/100 ft friction rate — the exact diameter works out to 8.8 in, at 679 fpm. For long or quiet runs, step up to 12 inches.

Size by design friction rate

Friction (in/100 ft)Exact ⌀Standard sizeVelocity (fpm)
0.0510.1 in12 in382
0.089.2 in10 in550
0.108.8 in9 in679
0.158.1 in9 in679

Rectangular options

Rectangular ducts equivalent to the 8.8-inch round requirement. Only buildable shapes are listed — nothing narrower than 4 inches or beyond a 4:1 aspect ratio.

Duct sizeEquivalent ⌀
12 × 6 in9.1 in
9 × 8 in9.3 in
10 × 7 in9.1 in
12 × 6 in9.1 in

FAQ

What size duct do I need for 300 CFM?
A 9-inch round duct at the standard 0.10 in. w.c. per 100 ft friction rate — the exact calculated diameter is 8.8 in, and the next standard size up is 9 in. Air moves through it at 679 fpm.
What if the run is long or noise matters?
Design at a lower friction rate. At 0.05 in/100 ft the same 300 CFM needs a 12-inch duct — larger, but quieter and with less pressure loss over a long run.
How many tons of cooling is 300 CFM?
At the standard 400 CFM per ton, 300 CFM corresponds to about 0.75 tons. Humid climates design closer to 350 CFM per ton, dry climates up to 450.

Other airflows: 200 CFM · 400 CFM · any airflow · standard sizes