Air distribution · Round duct

How many CFM does a 5 inch duct carry?

A 5-inch round metal duct carries about 67 CFM at the standard 0.10 in/100 ft friction rate, with the air moving at 492 fpm. Design it quieter at 0.05 and it carries about 47 CFM.

Airflow by design friction rate

Friction (in/100 ft)CFMVelocity (fpm)Typical use
0.0547342Long runs, quiet design
0.0860438Typical trunk
0.1067492Standard residential
0.1583609Short branch

Velocities above roughly 900 fpm get audible in a home; commercial mains tolerate more.

Rectangular equivalents

Rectangular ducts that match a 5-inch round, by Huebscher equivalent diameter. Only buildable shapes are listed — nothing narrower than 4 inches or beyond a 4:1 aspect ratio.

Width neededEquivalent ⌀
6 × 4 in5.3 in

FAQ

How many CFM can a 5 inch duct handle?
About 67 CFM at the standard residential design friction rate of 0.10 in. w.c. per 100 ft, moving at 492 fpm. Designed quieter at 0.05, the same duct carries about 47 CFM.
Is that figure for flexible duct too?
No — these numbers are for galvanized sheet metal. Flexible duct has noticeably more resistance, so a 5-inch flex run carries meaningfully less. Either size one diameter up or design the flex portion at a lower friction rate, and keep it pulled tight.
What size room does that serve?
At the usual 400 CFM per ton, 67 CFM is roughly 0.17 tons of cooling — enough for the branch serving one to two rooms in most homes, depending on the load.

Other sizes: 4 inch · 6 inch · ductulator · full chart