HVACCALCGet the iOS app

Air distribution · Duct sizing

What duct size for 2,500 CFM?

2,500 CFM needs a 20-inch round duct at the standard 0.10 in/100 ft friction rate — the exact diameter works out to 19.7 in, at 1,146 fpm. For long or quiet runs, step up to 24 inches.

Size by design friction rate

Friction (in/100 ft)Exact ⌀Standard sizeVelocity (fpm)
0.0522.6 in24 in796
0.0820.6 in22 in947
0.1019.7 in20 in1,146
0.1518.1 in20 in1,146

Rectangular options

Rectangular ducts equivalent to the 19.7-inch round requirement. Only buildable shapes are listed — nothing narrower than 4 inches or beyond a 4:1 aspect ratio.

Duct sizeEquivalent ⌀
36 × 10 in19.8 in
29 × 12 in19.9 in

FAQ

What size duct do I need for 2,500 CFM?
A 20-inch round duct at the standard 0.10 in. w.c. per 100 ft friction rate — the exact calculated diameter is 19.7 in, and the next standard size up is 20 in. Air moves through it at 1,146 fpm.
What if the run is long or noise matters?
Design at a lower friction rate. At 0.05 in/100 ft the same 2,500 CFM needs a 24-inch duct — larger, but quieter and with less pressure loss over a long run.
How many tons of cooling is 2,500 CFM?
At the standard 400 CFM per ton, 2,500 CFM corresponds to about 6.25 tons. Humid climates design closer to 350 CFM per ton, dry climates up to 450.

Other airflows: 2,000 CFM · 3,000 CFM · any airflow · standard sizes