Air distribution · Duct sizing

What duct size for 3,000 CFM?

3,000 CFM needs a 22-inch round duct at the standard 0.10 in/100 ft friction rate — the exact diameter works out to 21.1 in, at 1,136 fpm. For long or quiet runs, step up to 26 inches.

Size by design friction rate

Friction (in/100 ft)Exact ⌀Standard sizeVelocity (fpm)
0.0524.2 in26 in814
0.0822 in24 in955
0.1021.1 in22 in1,136
0.1519.4 in20 in1,375

Rectangular options

Rectangular ducts equivalent to the 21.1-inch round requirement. Only buildable shapes are listed — nothing narrower than 4 inches or beyond a 4:1 aspect ratio.

Duct sizeEquivalent ⌀
33 × 12 in21.1 in

FAQ

What size duct do I need for 3,000 CFM?
A 22-inch round duct at the standard 0.10 in. w.c. per 100 ft friction rate — the exact calculated diameter is 21.1 in, and the next standard size up is 22 in. Air moves through it at 1,136 fpm.
What if the run is long or noise matters?
Design at a lower friction rate. At 0.05 in/100 ft the same 3,000 CFM needs a 26-inch duct — larger, but quieter and with less pressure loss over a long run.
How many tons of cooling is 3,000 CFM?
At the standard 400 CFM per ton, 3,000 CFM corresponds to about 7.5 tons. Humid climates design closer to 350 CFM per ton, dry climates up to 450.