What duct size for 500 CFM?

500 CFM needs a 12-inch round duct at the standard 0.10 in/100 ft friction rate — the exact diameter works out to 10.7 in, at 637 fpm. For long or quiet runs, step up to 14 inches.

Size by design friction rate

Friction (in/100 ft)Exact ⌀Standard sizeVelocity (fpm)
0.0512.3 in14 in468
0.0811.2 in12 in637
0.1010.7 in12 in637
0.159.9 in10 in917

Rectangular options

Rectangular ducts equivalent to the 10.7-inch round requirement. Only buildable shapes are listed — nothing narrower than 4 inches or beyond a 4:1 aspect ratio.

Duct sizeEquivalent ⌀
18 × 6 in11 in
13 × 8 in11.1 in
10 × 10 in10.9 in
12 × 9 in11.3 in

FAQ

What size duct do I need for 500 CFM?
A 12-inch round duct at the standard 0.10 in. w.c. per 100 ft friction rate — the exact calculated diameter is 10.7 in, and the next standard size up is 12 in. Air moves through it at 637 fpm.
What if the run is long or noise matters?
Design at a lower friction rate. At 0.05 in/100 ft the same 500 CFM needs a 14-inch duct — larger, but quieter and with less pressure loss over a long run.
How many tons of cooling is 500 CFM?
At the standard 400 CFM per ton, 500 CFM corresponds to about 1.25 tons. Humid climates design closer to 350 CFM per ton, dry climates up to 450.

Other airflows: 400 CFM · 600 CFM · any airflow · standard sizes