Air distribution · Duct sizing
What duct size for 600 CFM?
600 CFM needs a 12-inch round duct at the standard 0.10 in/100 ft friction rate — the exact diameter works out to 11.5 in, at 764 fpm. For long or quiet runs, step up to 14 inches.
Size by design friction rate
| Friction (in/100 ft) | Exact ⌀ | Standard size | Velocity (fpm) |
|---|---|---|---|
| 0.05 | 13.2 in | 14 in | 561 |
| 0.08 | 12 in | 12 in | 764 |
| 0.10 | 11.5 in | 12 in | 764 |
| 0.15 | 10.6 in | 12 in | 764 |
Rectangular options
Rectangular ducts equivalent to the 11.5-inch round requirement. Only buildable shapes are listed — nothing narrower than 4 inches or beyond a 4:1 aspect ratio.
| Duct size | Equivalent ⌀ |
|---|---|
| 20 × 6 in | 11.5 in |
| 14 × 8 in | 11.5 in |
| 11 × 10 in | 11.5 in |
| 12 × 10 in | 12 in |
FAQ
- What size duct do I need for 600 CFM?
- A 12-inch round duct at the standard 0.10 in. w.c. per 100 ft friction rate — the exact calculated diameter is 11.5 in, and the next standard size up is 12 in. Air moves through it at 764 fpm.
- What if the run is long or noise matters?
- Design at a lower friction rate. At 0.05 in/100 ft the same 600 CFM needs a 14-inch duct — larger, but quieter and with less pressure loss over a long run.
- How many tons of cooling is 600 CFM?
- At the standard 400 CFM per ton, 600 CFM corresponds to about 1.5 tons. Humid climates design closer to 350 CFM per ton, dry climates up to 450.
Other airflows: 500 CFM · 800 CFM · any airflow · standard sizes